根據《供熱通(tong)(tong)(tong)(tong)風(feng)設計手(shou)冊》規范(fan)GBJ19-87和《DB42實驗室(shi)通(tong)(tong)(tong)(tong)風(feng)系統設計與施工(gong)規范(fan)》的(de)相(xiang)關規定(ding),確定(ding)通(tong)(tong)(tong)(tong)風(feng)柜、消化柜、原子吸收罩等通(tong)(tong)(tong)(tong)風(feng)設備(bei)、室(shi)內全面通(tong)(tong)(tong)(tong)風(feng)換氣(qi)的(de)通(tong)(tong)(tong)(tong)風(feng)量:
1) 設計中,按室(shi)(shi)內(nei)余熱、余濕、保證室(shi)(shi)內(nei)衛生條件的最小(xiao)換氣量進行計算。
一般(ban)性化(hua)學實驗室(shi)的通風量: 10-12次/小時
毒氣室、有(you)機合成、菌種培養的通風量:15-20次/小時
2) 通風柜(ju)(罩)排風工(gong)作面(mian)必(bi)須保持負壓狀態,通風柜(ju)面(mian)風速:
VAV狀態(tai) 0.5m/s±0.1m/s或根據用戶要(yao)求設(she)定其它值。
手動狀態0.3m/s~1m/s,視(shi)窗的(de)高低不影響(xiang)面所設定風速;
3) 通風系統使用終端噪音≤55dB ,通風柜面換氣次數:不小于15次;
4) 主(zhu)風(feng)(feng)(feng)管設計風(feng)(feng)(feng)速(su)小于9-12m/s,支風(feng)(feng)(feng)管設計風(feng)(feng)(feng)速(su)小于5-7m/s
5) 排風(feng)(feng)量:通風(feng)(feng)柜1500m3/h;
6) 快速執行器響應時間≤1s。
二、 透氣操作系統特殊要求1) VAV變(bian)風量變(bian)頻調節控制(zhi),保證系統多個通風柜(罩)同時(shi)運行時(shi),各自獨立(li)調節,不相互(hu)干擾(rao)。
2) 實驗室內(nei)氣流組織良好,氣流速度(du)及紊(wen)流度(du)均能控(kong)制在較(jiao)小的范(fan)圍內(nei),以免室內(nei)氣體(ti)的擾動引起排毒柜內(nei)氣體(ti)外(wai)溢。
3) 應(ying)有(you)不同型(xing)號和規格(ge)的(de)圓形或(huo)矩形單個變風量(liang)閥,滿足不同風量(liang)要求(qiu)并與設計圖紙相符合;
4) 結合(he)實驗室(shi)排風控(kong)制系統,包(bao)括變風量閥、消音器等(deng)能提供(gong)實驗室(shi)通(tong)風控(kong)制的完(wan)整解決(jue)方案(an)。
5) 實驗室風管在選擇(ze)防(fang)腐(fu)(fu)蝕較好(hao),硬度高的材質。本工程涉及到所有風管均可(ke)采用防(fang)腐(fu)(fu)蝕性(xing)能好(hao)的PVC/UPVC材質,風機全(quan)部為腐(fu)(fu)蝕性(xing)能好(hao)的玻璃(li)鋼風機。
6) 控(kong)制面(mian)板為漢字顯(xian)示,可顯(xian)示通風(feng)系統(tong)運行時的多項(xiang)信息。自動與手動多種工作模式可兼容設定,控(kong)制插座電源及照明的開(kai)啟(qi),可調節風(feng)閥角度(du)。
7) 實驗室內(nei)氣流(liu)組(zu)織(zhi)良(liang)好,送回風氣流(liu)速度及紊流(liu)度均(jun)能(neng)控制在較小的范圍內(nei),以免室內(nei)氣體的擾動引起排毒柜內(nei)氣體外溢(yi)。